Code | 99100012/13 | 99100101 | 99997355 |
Name | WATTMETRO TRIFASE PORTATILE | WATTMETRO TRIFASE DA RACK CON TA E TV EXT | VIW INTERFACE 3N HIGH PRECISION |
V in (V) | 115/230 V ± 10% – 50÷60 Hz | 110/220V±10%; 50÷60Hz | 90/265V RMS 50÷60Hz; 35 VA MAX |
V Range (Vrms full scale) | 150, 300, 600 | 20, 40, 80, 200, 400, 800 | 1Vpk to 3000Vpk (1000Vrms) in 8 ranges 20% over-range ability maintains 300Vpk range with 240Vrms |
I Range (Arms full scale) (1) | 2, 5, 10, 20, 50 | 2, 5, 10, 20, 50 | 100mApk to 300Apk (30Arms) in 8 ranges |
Power Range (W) | Single-phase connectors 0.3÷30 kW (30÷3000 W) Three-phase connectors 0.52÷52 kW (52÷5200 W) | 40 W÷40 kW | ~0,1W ÷ 30 kW |
Precision | ± 0.3% Full Scale | ± 0.3% Full Scale | Voltage Accuracy: 0.04% Rdg + 0.04% Rng + (0.004% x kHz) + 1mV (2) Current Accuracy: 0.04% Rdg + 0.04% Rng + (0.004% x kHz) + 100uA (2) Phase Accuracy: 0.04% Rdg + 0.04% Rng + (0.004% x kHz) + 1mV (2) 10 millidegrees + (20 millidegrees x kHz) (50Arms shunt) Watts Accuracy: [0.05% + 0.03%/pf +(0.01% x kHz)/pf] Rdg + 0.05%VA Rng DC Accuracy: Voltage – 0.1% Rdg + 0.1% Rng + 10mV (or 10uV external) Current – 0.1% Rdg + 0.1% Rng + 1mA (or 10uV external) |
Insulation | 3 kV rms for 60 sec. | ‘2000Vac, 60 sec. | Fully Isolated 1000V Cat II |
Manual | 62000230 | 62000310 | User Manual: 62000212 Communication Manual: 62000213 |
Brochure | VIW INTERFACE-T | VIW EURO ARON TA-TV EXT | Brochure VIV Interface 1N – 3N |
Accessories | 62000000 62000010 62000020 62000390 | 62000000 62000010 62000020 62000390 62000400 | |
|
F i l t e r s | R a n g e | Single-phase | | | |
Three-phase | ● | ● | ● |
S t r u c t u r e | PCB | | | |
Rack | | ● | |
Desk-top | ● | | |